PFAS in Veigné's tap water: under 3 ng/L, none of the four main PFAS detected

Last PFAS check: · Source: Hub'eau

PFAS in drinking water

None of the 4 most harmful PFAS detected

Amount found in the water < 3 ng/L the 4 most harmful PFAS (PFAS-4) · the lab's detection limit 20 PFAS looked for, 0.5 ng/L found in total
Our health benchmark 0.5 ng/L

The lab sees nothing below 3 ng/L, 6 times our benchmark of 0.5 ng/L. Water above our benchmark would pass this check unnoticed.

0.5 ng/L is our benchmark, not an official limit. Same EFSA method as Sweden, Denmark and the Netherlands, but stricter. It's a yearly average, compared here with the latest check.

Sample taken in Montbazon, on the same distribution network as Veigné (MONTBAZON). The health authority samples one tap per network; a network carries the same treated water everywhere.

More about this result

The US also limits PFOA and PFOS to 4 ng/L each, per substance.

The lab detects each of the four substances from 0.5 to 1.5 ng/L upward. None reached that limit, so their total is below 3 ng/L rather than zero.

20 PFAS (see each substance)
PFAS substance Value
Acide perfluoropentanoïque (PFPEA) 0.0005 µg/L
Acide sulfonique de perfluorooctane (PFOS) <0,0015 µg/L
Acide perfluoroheptanoïque (PFHPA) <0,001 µg/L
Acide perfluorododécanoique (PFDoDA) <0,0015 µg/L
Acide sulfonique de perfluorobutane (PFBS) <0,001 µg/L
Acide perfluoro tridecanoique (PFTrDA) <0,001 µg/L
Perfluorohexane sulfonate (PFHXS) <0,0005 µg/L
Acide perfluoro undecanoïque (PFUnA) <0,0015 µg/L
Acide perfluoro-octanoïque (PFOA) <0,0005 µg/L
Acide perfluoroheptane sulfonique (PFHpS) <0,001 µg/L
Acide perfluoro-decanoïque (PFDA) <0,0015 µg/L
Acide perfluorononane sulfonique (PFNS) <0,001 µg/L
Acide perfluoro undecane sulfonique (PFUnDS) <0,0015 µg/L
Acide perfluorohexanoïque (PFHXA) <0,001 µg/L
Acide perfluorobutanoïque (PFBA) <0,0015 µg/L
Acide perfluorodecane sulfonique (PFDS) <0,001 µg/L
Acide perfluorododécane sulfonique (PFDoDS) <0,0015 µg/L
Acide perfluoro-nonanoïque (PFNA) <0,0005 µg/L
Acide perfluoropentane sulfonique (PFPS) <0,001 µg/L
Acide perfluoro tridecane sulfonique (PFTrDS) <0,0015 µg/L

None found. The lab sees nothing below 3 ng/L, so our 0.5 ng/L benchmark cannot be checked.

EU legal limit
0.5 ng/L sum of 20 PFAS, below the 100 ng/L limit
Last PFAS test
18 June 2026
Water supplier
VEOLIA EAU CGE

In Veigné, none of the 4 most closely watched PFAS (PFAS-4) was detected at the latest PFAS check on 18 June 2026. The total is below 3 ng/L, the sum of the detection limits and 6 times our 0.5 ng/L benchmark. Sum of 20 PFAS: 0.5 ng/L (0.0005 µg/L), below the EU legal limit (100 ng/L). Sampled in Montbazon, on the same network. 5 checks since 12 June 2024: sum of 20 PFAS up to 0.7 ng/L, sometimes below the detection limit. Source: Hub'eau, Qualité de l'eau potable (Ministère de la Santé / OFB / BRGM).

Details and sources
Water supplier: VEOLIA EAU CGE Latest water check: 7 July 2026 Data updated on

PFAS over time in Veigné

5 PFAS checks since 12 June 2024, from the published measurements.

“Calculated”: PFAS-4 worked out from the four substances in the same sample. The chart, averages and trends use lab-published sums only.

1 ng/L012 June 202418 June 2026
Laboratory-published sum of 20 PFAS per check in ng/L. Hollow dots: below the detection limit. Calculated PFAS-4 values are listed in the table.
DatePFAS-4Sum of 20 PFASSampled at
< 3 ng/L · calculated0.5 ng/LMontbazon
< 3.5 ng/L · calculated0.7 ng/LMontbazon
< 10 ng/L · calculated< detection limitMontbazon
< 10 ng/L · calculated< detection limitMontbazon
< 10 ng/L · calculated< detection limitMontbazon

Calculated values: “<” is an upper bound from published thresholds, “≥” a lower bound, “–” means no published sum or complete measurement. How to read a PFAS result

What the latest check found

The authorities have not published an overall verdict for this water.

Microbiology: no verdict Chemistry: within the limit

Values to watch

These results are close to their legal limit, or over it.

Outside a reference value: Electrical conductivity 1,256 µS/cm on 7 July 2026 (reference 200–1,100 µS/cm). These are indicator parameters with reference values, not legal limits.

What was tested Value Limit Status
Fluoride 1.434 mg/L ≤ 1.5 mg/L within the limit
Electrical conductivity 1,256 µS/cm 200–1,100 µS/cm above the reference value
See all 19 test results
What was tested Value Limit Status
Nitrate 2.5 mg/L ≤ 50 mg/L within the limit
Nitrite <0,010 mg/L ≤ 0.5 mg/L within the limit
Lead 4.1 µg/L ≤ 10 µg/L within the limit
Copper 0.066 mg(Cu)/L ≤ 2 mg(Cu)/L within the limit
Nickel 7.1 µg/L ≤ 20 µg/L within the limit
Cadmium <0,010 µg/L ≤ 5 µg/L within the limit
Chromium 2 µg/L ≤ 50 µg/L within the limit
Fluoride 1.434 mg/L ≤ 1.5 mg/L within the limit
Escherichia coli <1 n/(100mL) ≤ 0 mL) within the limit
Enterococci <1 n/(100mL) ≤ 0 mL) within the limit
Coliform bacteria <1 n/(100mL) ≤ 0 mL) within the limit
pH 7.5 unité pH 6.5–9 unité pH within the limit
Water hardness 23 °f no limit for reference
Electrical conductivity 1,256 µS/cm 200–1,100 µS/cm above the reference value
Chloride 211 mg/L ≤ 250 mg/L within the limit
Sulphate 118 mg/L ≤ 250 mg/L within the limit
Sodium 154 mg/L ≤ 200 mg/L within the limit
Iron 2 µg/L ≤ 200 µg/L within the limit
Turbidity <0,30 NFU ≤ 2 NFU within the limit

Frequently asked questions

Is tap water in Veigné safe to drink?

The authorities have not published an overall verdict for this water. Outside a reference value: Electrical conductivity 1,256 µS/cm on 7 July 2026 (reference 200–1,100 µS/cm). These are indicator parameters with reference values, not legal limits. “Eau d'alimentation conforme aux limites de qualité et non conforme aux références de qualité pour le paramètre conductivité (mesure la quantité de minéraux dissous de l'eau). Cette situation a pour origine la nature de la ressource exploitée (nappe du cénomanien) et ne présente pas un danger pour la santé des consommateurs. Ce contrôle fait suite aux résultats d'analyses du prélèvement du 02/06/2026 qui présentaient une concentration en fluorures non conforme.”

How high are PFAS levels in Veigné's drinking water?

The total of 20 PFAS ("forever chemicals") was last measured at 0.5 ng/L. The EU limit is 100 ng/L, so this water is at 0.5 % of the limit. (below the EU limit)

Does the water in Veigné also meet the strictest limits in Europe?

As far as this check can tell, yes. None of the four compounds was quantified, so their total is below 3 ng/L, the sum of the laboratory's detection limits, and under Sweden's legal limit of 4 ng/L in force since 2026.

Are PFAS levels rising in Veigné's tap water?

Calculated PFAS-4 values are listed in the table. The chart uses laboratory-published sum-of-20 results; there are too few laboratory-published PFAS-4 sums for the existing trend calculation.

How hard is the water in Veigné?

The water hardness in Veigné is 23 °f (medium). This mainly matters for household appliances and detergent dosing, not for health.

Where does this data come from?

All values come from official publications: Hub'eau, Qualité de l'eau potable (Ministère de la Santé / OFB / BRGM). Retrieved on 21 September 2026.

Same water network

Same distribution network as Veigné, so in principle the same water.

Nearby communes

The closest to Veigné on this site.

Data source

Hub'eau, Qualité de l'eau potable (Ministère de la Santé / OFB / BRGM)
https://hubeau.eaufrance.fr/api/v1/qualite_eau_potable/resultats_dis?code_commune=37266
License
Licence Ouverte / Open Licence (Etalab)
Retrieved
21 September 2026
Supply networks
MONTBAZON

This site is a data project, not an official source. If in doubt, check with your water supplier or local authority.