PFAS in the tap water of Montot (Haute-Saône): no test result published yet

Last check: · Source: Hub'eau

Fails the current legal limits

PFAS in drinking water

No PFAS results have been published for Montot yet. Testing has been required across the EU since January 2026. We will show the values here as soon as they come out.

"Not published" does not mean "not present". Without test results, no one can say how much PFAS is in this water.

Fails a current legal limit. The details are below.

Latest water check
1 June 2026
Water supplier
MAIRIE DE MONTOT

No PFAS result is published for Montot in the data retrieved on 12 September 2026 (Hub'eau, Qualité de l'eau potable (Ministère de la Santé / OFB / BRGM)). PFAS testing of drinking water has been mandatory across the EU since January 2026. The latest published check dates from 1 June 2026.

Details and sources
Water supplier: MAIRIE DE MONTOT Latest water check: 1 June 2026 Data updated on

What the latest check found

At the latest check, the water was within every limit tested.

Microbiology: within the limit Chemistry: within the limit

Values to watch

These results are close to their legal limit, or over it.

Outside a reference value: Iron 419 µg/L on 1 June 2026 (reference ≤ 200 µg/L). These are indicator parameters with reference values, not legal limits.

What was tested Value Limit Status
Lead 25 µg/L ≤ 10 µg/L over the limit
Iron 419 µg/L ≤ 200 µg/L above the reference value
See all 20 test results
What was tested Value Limit Status
Nitrate <1,0 mg/L ≤ 50 mg/L within the limit
Nitrite <0,020 mg/L ≤ 0.5 mg/L within the limit
Lead 25 µg/L ≤ 10 µg/L over the limit
Copper 0.289 mg(Cu)/L ≤ 2 mg(Cu)/L within the limit
Nickel <5 µg/L ≤ 20 µg/L within the limit
Arsenic <2 µg/L ≤ 10 µg/L within the limit
Cadmium <1 µg/L ≤ 5 µg/L within the limit
Chromium <5 µg/L ≤ 50 µg/L within the limit
Fluoride 0.33 mg/L ≤ 1.5 mg/L within the limit
Escherichia coli <1 n/(100mL) ≤ 0 mL) within the limit
Enterococci <1 n/(100mL) ≤ 0 mL) within the limit
Coliform bacteria <1 n/(100mL) ≤ 0 mL) within the limit
pH 7.6 unité pH 6.5–9 unité pH within the limit
Water hardness 28.6 °f no limit for reference
Electrical conductivity 553 µS/cm 200–1,100 µS/cm within the limit
Chloride 3.8 mg/L ≤ 250 mg/L within the limit
Sulphate 21 mg/L ≤ 250 mg/L within the limit
Sodium 7.5 mg/L ≤ 200 mg/L within the limit
Iron 419 µg/L ≤ 200 µg/L above the reference value
Turbidity 0.66 NFU ≤ 2 NFU within the limit

Frequently asked questions

Is tap water in Montot safe to drink?

At the latest check, the water was over at least one limit. “En raison d'un excès de fer et/ou manganèse, l'eau peut présenter un goût métallique et une coloration qui tache le linge et les installations de plomberie. Les dépassements de la référence de qualité pour le fer deviennent de plus en plus récurrents sur les analyses d'eau brute et d'eau distribu ée. Cela peut témoigner d'un problème sous-jacent lié à l'exploitation de la nappe ou au forage. Il convient d'investiguer rapidement. Néanmoins, l'eau peut être consommée.”

How high are PFAS levels in Montot's drinking water?

No PFAS results have been published for Montot yet. Testing has been required across the EU since January 2026. We will show the values here as soon as they come out.

How hard is the water in Montot?

The water hardness in Montot is 28.6 °f (medium). This mainly matters for household appliances and detergent dosing, not for health.

Where does this data come from?

All values come from official publications: Hub'eau, Qualité de l'eau potable (Ministère de la Santé / OFB / BRGM). Retrieved on 12 September 2026.

Nearby communes

The closest to Montot on this site.

Data source

Hub'eau, Qualité de l'eau potable (Ministère de la Santé / OFB / BRGM)
https://hubeau.eaufrance.fr/api/v1/qualite_eau_potable/resultats_dis?code_commune=70368